The VEU series of aspirating smoke detectors are the premium detector of the VESDA-E range. An Ultra-wide sensitivity range; 15 times greater than VESDA VLP, and provision for more sampling holes provide an increased coverage in high airflow applications by at least 40%. Considerably longer linear pipe runs and extended branched pipe network configurations cater perfectly to applications with higher ceilings providing an increased coverage by up to 80% whilst allowing convenient detector mounting for ease of service and maintenance. A range of revolutionary new features provide unsurpassed detection performance, flexibility, field programmability, connectivity and reduced total cost of ownership.

Product Description
  • Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms
  • Short wavelength laser-based detection:
    • High sensitivity from small particle light scattering
    • No drift compensation required since focused light directed at target gives low backgrounds
    • High stability with temperature and time
  • Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance
  • Four alarm levels and an ultra wide sensitivity range deliver optimum protection for the widest range of applications
  • Intuitive LCD icon display provides instant status information for immediate response
  • Flow fault thresholds per port accommodate varying airflow conditions
  • Smart on-board filter retains dust count and remaining filter life for predictable maintenance
  • Extensive event log (20,000 events) for event analysis and system diagnostics
  • AutoLearn™ smoke and flow for reliable and rapid commissioning
  • Referencing to accommodate external environmental conditions to minimise nuisance alarms
  • Backward compatible with VLP and VESDAnet
  • Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance
  • USB for PC configuration, and firmware upgrade using a memory stick
  • Two programmable GPIs (1 monitored) for flexible remote control
  • Field replaceable sub-assemblies enable faster service and maximum uptime
  • Supply Voltage Range: 18–30 VDC (24V nominal)
  • Maximum Power Consumption:
    • VEU-A00-UL: 0.84A (quiescent), 0.88A (alarm)
    • VEU-A10-UL: 0.84A (quiescent), 0.88A (alarm)
  • Nominal Power Consumption @ 24V DC (Aspirator Settings 1 / 5 / 10):
    • VEU-A00-UL:
      • Quiescent: 0.29A / 0.38A / 0.61A
      • Alarm: 0.32A / 0.41A / 0.64A
    • VEU-A10-UL:
      • Quiescent: 0.32A / 0.41A / 0.64A
      • Alarm: 0.35A / 0.44A / 0.67A
  • Dimensions (W × H × D): 350 × 225 × 135 mm (13.8 × 8.9 × 5.3 in)
  • Weight: 5.3 kg (11.7 lbs)
  • Operating Temperature (Ambient): 0°C to 38°C (32°F to 100°F)
  • Sampled Air Temperature: -20°C to 60°C (-4°F to 140°F)
  • Humidity: 5% to 95% RH (non-condensing)
  • Maximum Coverage Area: 6,500 m² (69,965 sq. ft.)
  • Minimum Airflow per Pipe: 20 l/min
  • Pipe Length (Based on Number of Pipes):
    • 1 Pipe: 160 m (524 ft)
    • 2 Pipes: 150 m (492 ft)
    • 3 Pipes: 130 m (426 ft)
    • 4 Pipes: 95 m (312 ft)
  • Maximum Total Pipe Length (with branches): 610 m (2,001 ft)
  • Maximum Number of Sampling Holes: 96
  • Pipe Design Tool: ASPIRE
  • Pipe Size:
    • Inlet: 25 mm (1.05 in / ¾ in IPS)
    • Exhaust: 25 mm (1.05 in / ¾ in IPS) or via adaptor
  • Relays: 7 programmable relays (latching or non-latching)
  • Relay Rating: 2A @ 30 VDC (resistive)
  • IP Rating: IP40
  • Cable Access: 4 × 26 mm (1.02 in) entries
  • Cable Termination: Screw terminals (0.2–2.5 mm² / 24–14 AWG)
  • Measurement Range: 0.0000% to 11.09% obs/ft (0.000 to 32% obs/m)
  • Sensitivity Range: 0.0003% to 6.575% obs/ft (0.001% to 20.0% obs/m)
  • Threshold Settings:
    • Alert: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
    • Action: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
    • Fire 1: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
    • Fire 2: 0.0003%–6.575% obs/ft (0.001%–20.0% obs/m)
  • Event Log Capacity: Up to 20,000 events
  • Logged Data: Smoke levels, user actions, alarms, faults (time & date stamped)
  • AutoLearn Feature: Automatically sets alarm thresholds and airflow fault thresholds based on environmental conditions