WHAT WE’RE PRODUCTS
Sub Products
Product Details
VEU-A00-UL ASPIRATING SMOKE DETECTOR (HIGHEST SENSITIVITY ASD)


The VEU series of aspirating smoke detectors are the premium detector of the VESDA-E range. An Ultra-wide sensitivity range; 15 times greater than VESDA VLP, and provision for more sampling holes provide an increased coverage in high airflow applications by at least 40%. Considerably longer linear pipe runs and extended branched pipe network configurations cater perfectly to applications with higher ceilings providing an increased coverage by up to 80% whilst allowing convenient detector mounting for ease of service and maintenance. A range of revolutionary new features provide unsurpassed detection performance, flexibility, field programmability, connectivity and reduced total cost of ownership.
Product Description
- Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms
- Short wavelength laser-based detection:
- High sensitivity from small particle light scattering
- No drift compensation required since focused light directed at target gives low backgrounds
- High stability with temperature and time
- Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance
- Four alarm levels and an ultra wide sensitivity range deliver optimum protection for the widest range of applications
- Intuitive LCD icon display provides instant status information for immediate response
- Flow fault thresholds per port accommodate varying airflow conditions
- Smart on-board filter retains dust count and remaining filter life for predictable maintenance
- Extensive event log (20,000 events) for event analysis and system diagnostics
- AutoLearn™ smoke and flow for reliable and rapid commissioning
- Referencing to accommodate external environmental conditions to minimise nuisance alarms
- Backward compatible with VLP and VESDAnet
- Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance
- USB for PC configuration, and firmware upgrade using a memory stick
- Two programmable GPIs (1 monitored) for flexible remote control
- Field replaceable sub-assemblies enable faster service and maximum uptime
- Supply Voltage Range: 18–30 VDC (24V nominal)
- Maximum Power Consumption:
- VEU-A00-UL: 0.84A (quiescent), 0.88A (alarm)
- VEU-A10-UL: 0.84A (quiescent), 0.88A (alarm)
- Nominal Power Consumption @ 24V DC (Aspirator Settings 1 / 5 / 10):
- VEU-A00-UL:
- Quiescent: 0.29A / 0.38A / 0.61A
- Alarm: 0.32A / 0.41A / 0.64A
- VEU-A10-UL:
- Quiescent: 0.32A / 0.41A / 0.64A
- Alarm: 0.35A / 0.44A / 0.67A
- VEU-A00-UL:
- Dimensions (W × H × D): 350 × 225 × 135 mm (13.8 × 8.9 × 5.3 in)
- Weight: 5.3 kg (11.7 lbs)
- Operating Temperature (Ambient): 0°C to 38°C (32°F to 100°F)
- Sampled Air Temperature: -20°C to 60°C (-4°F to 140°F)
- Humidity: 5% to 95% RH (non-condensing)
- Maximum Coverage Area: 6,500 m² (69,965 sq. ft.)
- Minimum Airflow per Pipe: 20 l/min
- Pipe Length (Based on Number of Pipes):
- 1 Pipe: 160 m (524 ft)
- 2 Pipes: 150 m (492 ft)
- 3 Pipes: 130 m (426 ft)
- 4 Pipes: 95 m (312 ft)
- Maximum Total Pipe Length (with branches): 610 m (2,001 ft)
- Maximum Number of Sampling Holes: 96
- Pipe Design Tool: ASPIRE
- Pipe Size:
- Inlet: 25 mm (1.05 in / ¾ in IPS)
- Exhaust: 25 mm (1.05 in / ¾ in IPS) or via adaptor
- Relays: 7 programmable relays (latching or non-latching)
- Relay Rating: 2A @ 30 VDC (resistive)
- IP Rating: IP40
- Cable Access: 4 × 26 mm (1.02 in) entries
- Cable Termination: Screw terminals (0.2–2.5 mm² / 24–14 AWG)
- Measurement Range: 0.0000% to 11.09% obs/ft (0.000 to 32% obs/m)
- Sensitivity Range: 0.0003% to 6.575% obs/ft (0.001% to 20.0% obs/m)
- Threshold Settings:
- Alert: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
- Action: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
- Fire 1: 0.0003%–0.614% obs/ft (0.001%–2.0% obs/m)
- Fire 2: 0.0003%–6.575% obs/ft (0.001%–20.0% obs/m)
- Event Log Capacity: Up to 20,000 events
- Logged Data: Smoke levels, user actions, alarms, faults (time & date stamped)
- AutoLearn Feature: Automatically sets alarm thresholds and airflow fault thresholds based on environmental conditions