WHAT WE’RE PRODUCTS

Sub Products

Product Details

SS-8ZE 8 ZONE FIRE ALARM CONTROL PANEL

Honeywell System Sensor Fire Alarm Control Panels have been developed to provide a simple and reliable solution to the demands of today’s fire detection solutions. The panels have been designed with both installer and end user’s requirements in mind suited for small to medium sized buildings like Commercial Buildings, Banking, Residential complexes, Retail Units/ Stores, Shops, Restaurants, Healthcare, Public Offices, Schools etc

For installers, Honeywell System Sensor panels offer an out of the box and on the wall solution. A combination of quick installation, an enhanced feature set and advanced programming allows installers to quickly and simply meet the demands of the user. Equipped with programmable relays, delay setting for alarm verification, software isolation of zone and NAC output, provide wide variety of choice for system installers to customize the need of an end user.

Engineered and built to the same high standard as all Honeywell Fire Control panels, this System Sensor panel forms an essential part of any fire detection requirement

Product Description

Low profile design
• Low current draw
• Backward compatible with Series 100 detector range
• Wide operating voltage 8 to 30VDC
• Bi-colour LED detector status indicator
• Automatic drift compensation
• Programmable sensitivity
• Addressable feature
• Advanced maintenance features via remote
• Range of detector bases available
• Tested and approved to EN54 – 7:2000 (Amendment
EN54 – 5:2000 Class A1R; (Amendment 1) CEA4021

Mechanical Specifications
Dimensions (H X W X D)
360 X 422 X 122.8 mm (Front Facia),
360 X 380 X 92.3 mm (Back Box)
Weight
5.8 Kg Approx. (No Battery Fitted)
Construction
Powder coated Cold Rolled STEEL 1.2mm thick
Cable Entry
15 X 20mm Knockout
Operating Temperature
0 to 49°C
Relative Humidity
5% to 95% Non-Condensing

Electrical Specifications

Operating Voltage
230V-AC +/- 20% Output current 2A
maximum, Alarm Load 1A Maximum
Standby Batteries
Minimum capacity 2 x 12 V 2.8Ah, Maximum capacity 2 x 12 V 7 Ah
Detection Circuits
2, 4, 6, 8 zone, Max 2mA per Detector Circuit
Input Trigger Extended closing contact
Trigger External Outputs
Sounder Outputs:
• 2 monitored outputs
• 0.5 Amps per circuit
Auxiliary Output:
• 18.5 to +28.5 Vdc, 0.5 Amp. (max)