SS/4ZVS 4 ZONE CONVENTIONAL PANEL


Honeywell Conventional Fire Alarm Control Panels are developed to provide a simple and reliable solution to meet the basic demands of fire detection requirements. The panels are also been designed to meet the requirements of both installer and end user. The Fire Alarm Control Panel are suited for small to medium sized buildings like small offices, banks, retail units/stores, shops, restaurant, small healthcare facilities, pre-schools, etc.
A combination of quick installation, an enhanced feature set and simple programming allows installers to quickly meet the demands of the user. Equipped with delay setting for alarm verification, programmable, relay, NAC output and password protection provide wide variety of choice for system installers to customize the need of an end user. Engineered and built to the same high standard as all Honeywell Fire Control panels, this panel forms an essential part of any fire detection requirement.
Product Description
• ThreeForm-Crelays(1Fire, 1 Fault and1Programmable 2amps@30VDC)
• 1 On-board NACs operating @ 0.5A/circuit
• Aux Output: 24VDC
• Sounder Output: 24VDC
• Feature Detection Circuits: 2 & 4 Zones (upto 20 Detectors + 5 MCPs)
• Zone wiseFire,Fault, Disable indication
• Panel keys: SilenceBuzzer/Alarm; Reset; Navigation keys (Left,Right, Down, Menu/Ok)
• Lamp Test & Walk Test
• Evacuate
• Supports standbypower24VDC(2no’sof12V, 7AhLead AcidBattery)
• Event Log-1200 events
• Earthfaultmonitoring
| Specification | Details |
|---|---|
| Dimensions (L × B × H) | 325 × 250 × 93 mm |
| Weight | Net: 3.00 kg; Gross: 3.75 kg approx. (No battery fitted) |
| Construction | Cold Rolled Steel with powder-coated finish and door lock |
| Cable Entry | 08 × 20.50 mm Knockouts |
| Operating Temperature | 0°C to 49°C / 32°F to 120°F |
| Relative Humidity | 5% to 95% Non-Condensing |
| Detection Circuits | 2 or 4 Zone |
| Detection Circuit Type | Class B Circuit |
| Maximum Zone Current | 2 mA per Zone |
| Operating Voltage | 230 VAC, 50 Hz |
| Alarm Load (Sounder) | 0.5 Amp max. |
| NAC Output | 0.5 Amp max. |
| Device Standby Current | 50 mA maximum |
| Standby Batteries – Minimum | 2 × 12 V, 2.8 Ah |
| Standby Batteries – Maximum | 2 × 12 V, 7 Ah |
| Sounder Output | 18.5 to 28.0 VDC, 0.5 Amp max. |
| Auxiliary Output | 18.5 to 28.0 VDC, 0.5 Amp max. |
| Recommended Zone Wiring | 1.0 sq. mm multicore, flame-retardant cable (Standard ISI-marked cable) |
| Recommended NAC Wiring | 1.5 sq. mm multicore, flame-retardant cable (Standard ISI-marked cable) |