WHAT WE’RE PRODUCTS

Sub Products

Product Details

RE-104-R 4 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL

The RE-102R & RE-104R is a 2 & 4 Zone Fire Alarm Control Panel,
which uses conventional input devices. The Outputs include Notification
Appliance Circuits (sounders), two programmable Form – C relays, RS-485
port to interface with annunciators and optional zone wise sounder & zone
wise contact. The FACP is field programmable via the panel keypad. It also
supervises all wiring, AC voltage and battery level. Optional ethernet, &
GSM ports are user for transmission.
This Fire Alarm Control panel is designed to be used for small size
commercial buildings and small-scale industries.

Product Description

– CE Approved.
– 16 X 2 Dot Matrix LCD Display.
– Standby battery backup with built in charging.
– Switch Mode Power Supply.
– Tactile Keypad for easy panel operation.
– System ON indication.
– Low Battery visual warning with audible tone.
– Fire / Fault status in unambiguous colored LED indication.
– 2 programmable relays for fire, supervisory and fault.
– All zones accept smoke detectors and any normally open contact device.
– Any Zone can be configured as alarm or supervisory.
– Zone wise isolation and one man walk test facility.
– Programmable Aux Outputs.
– Lamp test & Drill test facility.
– 100 All Events log with RTC.
– Date / Time / Password configuration.
– Programmable auto silence facility.
– Zone wise sounder / contact (optional).
– TCP-IP / GSM facility (optional).
– All field wiring circuits are supervised.

Technical Specifications

Power

Parameter Specification
Primary Power 120 / 230 VAC +10% –15%, 60 / 50 Hz, 50W
Standby Power 24VDC (2 × 12V, 3.5Ah Sealed Lead Acid Battery)

Operating Conditions

Parameter Specification
Operating Temperature 0 – 49°C / 32 – 120°F
Storage Temperature 0 – 60°C
Relative Humidity 93 ± 2% RH (non-condensing) at 32 ± 2°C / 90 ± 3°F

Quiescent Current

Model / Zones Current
2 Zone 40 mA
4 Zone 50 mA

Charging Circuit

Parameter Specification
Charging Voltage 28V ± 5%
Charging Current 350 mA (max)
Operating Voltage 24VDC
Quantity 1 No

Auxiliary Power Output

Parameter Specification
Voltage 24VDC continuous or resettable (Regulated)
Current 100 mA (max)

Notification Appliance Circuits (NAC)

Parameter Specification
Wiring Style Class B
Quantity 1 No
Operating Voltage 24VDC (Regulated)
Current 350 mA
EOL Resistor 4K7, ½ watt

Relays

Parameter Specification
Type Form C
Quantity 2 Nos (Programmable)
Relay Contact Rating 1A @ 30 VDC
Power Factor 1.0