WHAT WE’RE PRODUCTS

Sub Products

Product Details

NFS-320 ONE LOOP FIRE ALARM ALARM CONTROL PANEL

The NFS-320 intelligent Fire Alarm Control Panel is part of the
ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products meet virtually every application requirement.
The NFS-320’s modular design makes system planning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the application. Wireless fire pro- tection can be added with the SWIFT wireless gateway and devices.
For installations using NFS-320C, an optional ACM Series annunciator can be mounted in the same cabinet (up to 48 zones/points, order separately; see DN-60085).

Product Description

• Certified for seismic applications when used with the appro- priate seismic mounting kit.
• Approved for Marine applications when used with listed com- patible equipment. See DN-60688.
• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7.
• Up to 159 detectors and 159 modules per SLC; 318 devices maximum.
– Detectors can be any mix of ion, photo, thermal, or multi- sensor; wireless detectors are available for use with the
FWSG.
– Modules include addressable pull stations, normally open contact devices, two-wire smoke detectors, notification, or
relay; wireless modules are available for use with the FWSG.
• Optional FWSG Wireless SWIFT Gateway supports wireless SLC devices.
• Standard 80-character display.
• Network options:
– High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks,
NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYX-
Works, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP- 300/400, AFP-1010, and AM2020). Up to 54 nodes when
DVC-EM is used in network paging – Internet/GSM
• 80-character remote annunciators (up to 32).
• EIA-485 annunciators, including custom graphics.
• Printer interface (80-column and 40-column printers).
• History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file.
• Alarm Verification selection per point, with automatic counter.
• Presignal/Positive Alarm Sequence (PAS).
• Silence inhibit and Auto Silence timer options.
• NAC coding functions:
– March time.
– Temporal.
– California two-stage coding.
– Canadian two-stage.
– Strobe synchronization.
• Field-programmable on panel or on PC with VeriFire® Tools program check, compare, simulate.
• Full QWERTY keypad.
• Battery charger supports 18 – 200 AH batteries.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor modules.
• Automatic time control functions, with holiday exceptions.
• Extensive, built-in transient protection.
• Powerful Boolean logic equations.

FLASHSCAN® INTELLIGENT FEATURES
• Polls up to 318 devices in less than two seconds.
• Activates up to 159 outputs in less than five seconds.
• Multicolor LEDs blink device address during Walk Test.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• Manual sensitivity adjustment — up to nine levels.
• Pre-alarm ONYX intelligent sensing — up to nine levels.
• Day/Night automatic sensitivity adjustment.
• Sensitivity windows:
– Ion – 0.5 to 2.5%/foot obscuration.
– Photo – 0.5 to 2.35%/foot obscuration.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.

Program Keypad: QWERTY type (keyboard layout).
12 LED Indicators: Power; Fire Alarm; Pre-Alarm; Security; Supervisory; System Trouble; Signals Silenced; Points Disabled; Control Active; Abort; Pre-Discharge; Discharge.
Keypad Switch Controls: Acknowledge/Scroll Display; Signal
NFS-320: The standard, factory-assembled NFS-320 system includes the following components: one control panel mounted on chassis (120 V operation — ships with grounding cable, bat- tery interconnect cables, and document kit); includes integral power supply mounted to the main circuit board; one primary display KDM-R2 keypad/display; and one cabinet for surface or semi-flush mounting. Purchase batteries separately. One or two option boards may be mounted inside the NFS-320 cabinet; additional option boards can be used in remote cabinets. (Non- English versions also available. NFS-320-SP,NFS-320-PO.)
NFS-320R: Same as NFS-320, but in red enclosure.
NFS-320C: Based on NFS-320 above. NFS-320C supports installation of an optional ACM-series annunciator in the same cabinet. UL- and ULC-listed. (Non-English version also avail- able: NFS-320C-FR.) For NFS-320C, see DN-60085.
NFS-320CR: Same as NFS-320C but in a red enclosure. For
NFS-320C, see DN-60085.
NFS-320E: Same as NFS-320, but with 240 V operation. (Non- English versions also available. NFS-320E-SP, NFS-320E-PO.)
TR-320: Trim ring for the NFS-320 cabinet.

NETWORKING OPTIONS

NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN-6861.
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network Communications Modules. Wire, single-mode fiber, multi-mode fiber, and media conversion models are available. See DN- 60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN-6971.

Open chat
Hello 👋
Can we help you?