WHAT WE’RE PRODUCTS
Sub Products
Product Details
VESDA E-VEP ASPIRATING SMOKE DETECTOR
The VESDA-E VEP series of smoke detectors bring the latest and most advanced detection technology to provide very early warning and the best nuisance alarm rejection to a wide range of applications. Built on the Flair detection technology and years of application experience, VEP detectors achieve consistent performance over their lifetime via absolute calibration. In addition, the VEP delivers a range of revolutionary features that provide user value.
Model Nos. VEP-A00-1P, VEP-A00-P, VEP-A10-P
Product Description
One and four pipe models for different applications
Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms
Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance
Four alarm levels and a wide sensitivity range deliver optimum protection for the widest range of applications
Intuitive LCD icon display provides instant status information for immediate response
Flow fault thresholds per port accommodate varying airflow conditions
Smart on-board filter retains dust count and remaining filter life for predictable maintenance
Extensive event log (20,000 events) for event analysis and system diagnostics
Auto Learn™ smoke and flow for reliable and rapid commissioning
Referencing to accommodate external environmental conditions to minimize nuisance alarms
Fully backward compatible with VLP and VESDA net
Remote monitoring with VESDA for system review and proactive maintenance
Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance
Industry first. Aspirating detector secondary monitoring and maintenance via WiFi
USB for PC configuration, and firmware upgrade using a memory stick
Two programmable GPIs (1 monitored) for flexible remote control
Field replaceable sub-assemblies enable faster service and maximum up time
Supply Voltage 18-30 Vdc (24V Nominal)
Power Consumption @ 24Vdc Aspirator Setting
VEP-A00-1P: Fixed
VEP-A00-P & VEP-A10-P: 1-5
Power (Quiescent)
VEP-A00-1P: 8.8w
VEP-A00-P: 7.0 – 8.8w
VEP-A10-P: 8.2w – 10.0w
Power (In Alarm)
VEP-A00-1P: 9.6w
VEP-A00-P: 7.8w – 9.6w
VEP-A10-P: 10.4w – 11.6w
Dimensions (W x H x D) 350 mm x 225 mm x 135 mm (13.8 in x 8.9 in x 5.3 in)
Weight VEP-A00-1P: 4.0 kg (8.8 lb)
VEP-A00-P: 4.0 kg (8.8 lb)
VEP-A10-P: 4.1 kg (9.0 lb)
Operating Conditions Ambient: 0°C to 39°C (32°F to 102°F)
Sampled Air: -20°C to 60°C (-4°F to 140°F)
Tested to: -20°C to 55°C (-4°F to 131°F), UL: -20°C to 50°C (-4°F to 122°F)
Humidity: 10% to 95% RH, non-condensing
Area Coverage VEP-A00-1P: 1,000m2 (10,760 sq.ft)
VEP-A00-P & VEP-A10-P: 2,000m2 (21,520 sq.ft)
Minimum airflow per pipe 15 l/m
Pipe Length (Linear) VEP-A00-1P: 100 m (328ft)
VEP-A00-P & VEP-A10-P: 280 m (919ft)
Pipe Length (Branched) VEP-A00-1P: 130m (427ft)
VEP-A00-P & VEP-A10-P: 560m (1,837ft)
Pipe lengths depending on number of pipes in use
VEP-A00-1P: 100m (328ft)
VEP-A00-P & VEP-A10-P
1 Pipe: 110m (361ft)
2 Pipe: 100m (328ft)
3 Pipes: 80m (262ft)
4 Pipes: 70m (230ft)
Number of Holes VEP-A00-1P
Class A: 30
Class B: 40
Class C: 45
VEP-A00-P & VEP-A10-P
Class A: 40
Class B: 80
Class C: 100
Computer Design Tool ASPIRE
Pipe Inlet: External diameter 25mm or 1.05in (3/4in IPS)
Exhaust: External diameter 25mm or 1.05in (3/4in IPS) via adaptor
Relays 7 programmable relays (latching or non-latching states)
Contacts rated 2A @ 30Vdc (Resistive)
IP Rating IP40
Cable Access 4 x 26mm (1.02in) cable entries
Cable Termination Screw terminal blocks 0.2–2.5sq mm (24–14 AWG)
Dynamic Range 0.001% to 32% obs/m (0.0003% to 10% obs/ft)
Sensitivity Range 0.005 to 20% obs/m (0.0016% to 6.25% obs/ft)
Threshold Setting Range Alert: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)
Action: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)
Fire1: 0.010% to 2.0% obs/m (0.0031% to 0.625% obs/ft)
Fire2: 0.020% to 20.0% obs/m (0.0063% to 6.25% obs/ft)
Software Features Event log: Up to 20,000 events
Smoke level, user actions, alarms and faults with time and date stamp
Auto Learn: Detector learns Alarm Thresholds and Flow Fault thresholds by monitoring the environment