ULCF3000- PRG UL LOOP MOUNTED REPEATER PANEL
The ULCF3000PR passive repeater panel, is a cost effective system which can be programmed via its informative display to be either fully passive (display only) or semi passive (restricted system control).
When loop connected the repeater panel will display the system information text of the connected control panel and will provide a fire indication, with panel number, of any connected network control panel that has fire activation.
The ULCF3000PR repeater panel does not require system programming, with the exception of local text information.
In addition to this repeater panels main menu driven 2 x 40 backlit LCD display, which provides system status information, it also has 6 supervisory LED’s (Power On, Alarm, Trouble, Supervisory, Test In Progress, and Scroll)
Product Description
Fully passive
Up to 200 Repeaters can be connected to the loop
Surface or semi-recessed mounting
2 x 40 backlit LCD display and 6 supervisory LED’s
Compact size
Benefits
Menu driven easy to operate
Simple connection to panel SLC circuit reduces wiring and time
Distance run up to 2kms from main panel without additional cable and equipment, saving cost
Code
ULCF3000PR
Description
Passive Repeater Panel
Standards
UL864 9th edition
System Indicators
LED’s
Power on, Alarm, Trouble, Test, Supervisory, Scroll LED’s
Mains Input, Supervised
Voltage
120 V ac to 240 V ac, 60 Hz
Current
35 mA
SLC Field Wiring
Current
0.354 mA
Wiring Gauge
12 (max) AWG
Wiring Class
Class A Style 7
Ground Fault
0.1 ohm
Supervisory, Power Limited
Yes
Line Impedance
50 Ω (max)
Batteries
Batteries
1×12 V dc, 3.2 Ah, 0.1 derating
Battery Charge Current
0.4 A
Standby Period
24 hours + 30min alarm
Download Comms
RS232 port
Environmental
Operating Temperature
0°C to 49°C
Humidity (Non Condensing)
0 to 93 %RH
Physical
Dimensions (H x W x D)
270mm x 332mm x 90mm
Weight
3.6kg (with batteries)
Ingress Protection
IP30
Construction
PC/ABS, UL94 5VA rating
Colour
Light Grey or Graphite
Cable Entry
12 x 20mm knockouts top of backbox
Compatibility
Suitable for use with
Eaton’s UL fire systems