SMX- 2 Loop 396 Devices UL-Listed
The SMX Series is designed keeping in mind the needs of today’s performance conscious establishments. It is a range of compact and feature-rich, modern-age panels that constitute together with a suite of intelligent devices, highly reliable fire alarm systems.
The SMX panels meet the requirements of the latest codes and standards and allow for quick and easy installation. Just fix the panel to the wall, connect the field wiring devices, and power up the panel for a working fire alarm system. The large touch display allows the panel to be programmed easily by providing a clear menu structure, making the the entire setup process extremely intuitive. Complex configuration is made easy by using the mobile appl and the Bluetooth dongle connectivity.
USER INTERFACE
Display: 5-inch multi-color touch display
Control Keys: Silence Buzzer, Silence/Resound Alarm, Reset
Indicators: Power, Alarm Silenced, Trouble, System Trouble, Disabled Test Supervisory, Delay
DEVICES AND LOOP CAPACITY
Supports Morley IAS UL detectors & modules
Loop Capacity: 500 mA per loop
Product Description
• Multiple loop options – 1, 2, and 4 loops
• Up to 198 devices per full loop
• 160 fire zones
• 10,000 events log
• Multiple output and input interfaces for
• Pluggable electrical connectors and ergonomic design for easy installation
• Large touch display for enhanced readability, context-awareness and easy navigation resulting in exemplified user
experience
• Ability to configure panels off-site and sync via USB pen drive or Honeywell Bluetooth
• Battery-backed, real-time clock (RTC)
• 32-bit dual-core microprocessor
• Mobile and PC apps for guided configuration
• UL 864 10 Edition Certified
INTERFACES
• 3 Output Relays with single pole changeover 24V DC 1 A: Fire Trouble & Programmable (Supervisory by default)
• 1 RS485 port for up to 8 repeaters or mimics or a combination of the two
• 1 RS232 ports: One for serial printer
• 2 USB ports: One for pen drive and Honeywell Bluetooth dongle and one reserved for future use
• 2 NAC circuit with max 150 mA each
• 2 on-board monitored inputs
ELECTRICAL SPECIFICATIONS
OPERATING VOLTAGE 230V AC, 50/60 Hz
PSU RATING 24V DC 6.5 A
STAND-BY BATTERIES 2 loop (915-100-102) – 2 x 12Ah
4 loop (615-000-202) – 2 x 18 Ah or 2 x 24 Ah
(based on battery back-up calculations)
STAND-BY BATTERY DURATION 24 hours back-up under normal condition
AUXILLIARY OUTPUT 2 units of 24 V Dc 100 mA each
FIELD STRENGTH 52V/m for 5W test condition
Agency Listings and Approvals
Listing and approval below apply to the modules specified in this. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: S36244