WHAT WE’RE PRODUCTS

Sub Products

Product Details

RE-25AR 4 ZONE GAS RELEASE PANEL

RE25AR Gas Release Panel fully
complies with UL -864 and NFPA-72. It is
a feature-packed control unit performing
dual function of detection and controlled
release of gaseous agent.

Product Description

Rugged CRCA sheet with powder coated finish.
16×2 Dot Matrix LCD Display.
Operates on 120-220v 60 / 50 Hz, AC Mains power
supply.4 Class B initiating device circuit (IDC).
All zones accept smoke detectors and any normally open Contact device.
Any Zone can be configured as Alarm or supervisory Zone.
2 Class B Releasing Agent Circuits (RAC).
2 Class B Notification Appliance Circuits (NAC).
Standby (battery) backup 24v DC power supply with builtin charger
Error free Fire / Fault status in unambiguous colored LED indication.
System ON indication.
Main, Standby status audible and visual indication.
Battery Low visual warning with audible tone.
3 Form C programmable relays for Fire / fault / supervisory / Gas Released.
Programmable two Input Circuits for Manual release and Abort.
Two modes of operations Auto / Manual.
Programmable 24v D.C Outputs.
RS 485 Communication facility (Optional). MODBUS (Optional).
Events history log with RTC.
Walk Test facility.
Zone Isolation facility.
Earth fault annunciation facility.
All field wiring circuits are Power limited except 220v AC
and Battery.
All field wiring circuits are supervised.
AC Low voltage cutoff.
Alarm verification facility .

Specification
Primary Power (RE-SMPS-4A-R1)
120 – 220VAC ± 10%, 50 Hz, 2.5Amps.
Standby Power
24v D.C (2 Nos of 12v, 12Ah Sealed Lead acid battery).
Operating Condition
Operating Temperature 0 – 49° C/32-120° F. Relative Humidity 93 ± 2% RH (non-condensing) at 25 ±2° C/77 ±3° F.
Charging Circuit
Charging Voltage 28.4V, ±0.2V With current
800mA (Max).
D.C. Output Power
Supervised 24VDC regulated, 1A Max. (for 4 wire smoke detector)
Common Four Form C Relays
Relay Contact Rating: 2Amps @ 30 VDC, 0.5Amps @ 125VAC.
Power Factor: 0.6
Dimension of the panel :
450 x 340 x 120 mm ( length x height x width )

Initiating Device Circuits
All Zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage: 14 – 21 VDC. Alarm Current: 15 – 30mA.
Short Circuit Current: 45mA Maximum. Loop resistance: 100 ohms Maximum. End-Of-Line Resistor: 3K9, 1/2watt
Standby Current: 7mA (2mA for Detectors)
Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage: 24VDC Special
Application
Current for NACs: 0.6A per circuit
Line Drop: 1.8V
End-Of-Line Resistor: 3K9, 1/2watt
Releasing Agent Circuits
Class B Style – Y wiring
Operating Nominal Voltage: 24VDC Special
Application
Current for RACs: 0.6A per circuit
Line Drop: 1.8V
End-Of-Line Resistor: 3K9, 1/2watt.