WHAT WE’RE PRODUCTS
Sub Products
Product Details
RE-9012 12 ZONE FIRE ALARM CONTROL PANEL
RE-9012 is a Microprocessor based
conventional Fire Alarm Control Panel, are
designed to be used for medium and large size
commercial complexes and industrial
establishments. These panels are user friendly
system such as touch keypad to program panel.
This can be used as a standalone or networkable
Product Description
* Complies with UL -864 and NFPA-72.
* Operates on 120 – 220v 60 /50 Hz, AC Mains power supply.
* Standby (battery) backup 24v DC power supply with built-in charger.
* Touch Keypad for user friendly operation.
* Epoxy powder coated finish.
* Class- B, Style B / C initiating device circuit (IDC).
* All zones accept smoke detectors and any normally open contact device.
* Class B Notification Appliance Circuits (NAC).
* NAC shall be programmed as auto silence / Silence Inhibit.
* Error free Fire / Fault status in unambiguous colored LED indication.
* 1000 Event storage with RTC.
* Main, Standby status with audible and visual indication.
* Two Form C relays for fire and fault.
* Resettable / Steady 24V D.C. Output.
* RS 485 Communication facility.
* TCP/IP facility (Optional)
*MODBUS for BMS integration (Optional).
* PC software (optional)
* External Zone Wise Sounder/Contact via RS 485 (Optional).
* All field wiring circuits are supervised.
* Zone Isolation facility with loop voltage cut off.
* Facility to connect Public Address System (PA) through RS-485 Communication.
* Maximum 16 panels can be connect in a Single Network.
Electrical Specifications – Tabular Format
Primary Power
| Parameter | Specification |
|---|---|
| Input Voltage | 120 – 220VAC ±10% |
| Frequency | 60 / 50 Hz |
Standby Power
| Parameter | Specification |
|---|---|
| Standby Power | 24VDC |
| Quiescent Current | 120 mA |
Operating Conditions
| Parameter | Specification |
|---|---|
| Operating Temperature | 0 – 49°C / 32 – 120°F |
| Relative Humidity | 93 ± 2% RH (non-condensing) at 32 ± 2°C / 90 ± 3°F |
Charging Circuit
| Parameter | Specification |
|---|---|
| Charging Voltage | 28.0V ± 0.5V |
| Charging Current | 1.2A (Max) |
D.C. Output
| Parameter | Specification |
|---|---|
| Type | Resettable / Steady |
| Output | 24VDC |
| Max Current | 1A |
Common Relays
| Parameter | Specification |
|---|---|
| Type | Form C |
| No. of Relays | 2 |
| Relay Contact Rating | 2A @ 30VDC, 0.5A @ 125VAC |
| Power Factor | 1.0 |
Initiating Device Circuits
| Parameter | Specification |
|---|---|
| Zones | All zones |
| Wiring Style | Class B Style B/C (Programmable) |
| Operating Voltage | 14 – 21 VDC |
| Alarm Current | 15 – 30mA |
| Short-Circuit Current | 45mA Max |
| Loop Resistance | 100Ω Max |
| EOL Resistor | 4K7, ½ watt |
| Standby Current | 7mA (2.5mA for detectors) |
Notification Appliance Circuits (NAC)
| Parameter | Specification |
|---|---|
| Wiring Style | Class B Style – Y Wiring |
| Operating Voltage | 24VDC |
| Special Application Current | 2 Amps (1A per circuit) |
| Line Drop | 1.8V |
| EOL Resistor | 4K7, ½ watt |
Dimensions
| Parameter | Specification |
|---|---|
| Cabinet Size | 425W × 350H × 120D mm |
Ordering Information
| Model | Description |
|---|---|
| RE-9012 | 12 Zone Fire Alarm Control Panel |
Compatible Devices
| Model | Description |
|---|---|
| RE-900RP Series | Fire Alarm Repeater Panel |