RA-2000 Remote Annunciator
The RA-2000 or RA-2000GRAY remote annunciators can be used to operate and program the Honeywell Farenhyt Series FACPs. The RA-2000 features a large, 4 x 40 display and four programmable buttons. These features provide more options for set-up and operation when compared to similar remote annunciators.
The RA-2000 is shipped in a locked, key controlled cabinet, combining security with easy access. It does not require a code or firefighter’s key to silence or reset a panel. In addition, it is designed with convenient separate scroll buttons to be used for alarm, supervisory and trouble conditions. The remote annunciator communicates with the main fire alarm control panel through an RS-485 connection. The RA-2000 can be surface- or flush-mounted and is available in gray as the RA-2000GRAY.
Product Description
â˘Â  Complies with UL 864 10th and UL 2572 | â˘Â  Includes four programmable function keys | â˘Â  Uses the following five status LEDs: |
2nd Edition Standards | â˘Â  Displays the status and event history of all | – alarm |
â˘Â  Complies with NFPA 72 | the panels they are assigned in a network | – supervisory |
â˘Â  Features a four-line LCD display with 40 | â˘Â  Multi-panel annunciators will sound the | – trouble |
characters per line | highest  priority tone from the panel it is | – silence |
â˘Â  Designed with a tactile/audible feedback | assigned | – AC power indications |
when the key is pressed on the annunciator | â˘Â  Available in red or gray color | â˘Â  View current status by alarms, supervisories, |
â˘Â  Has an RS-485  SBUS interface to panel | â˘Â  Provides onboard piezo sounder to | or troubles |
â˘Â  Initiate and end fire drills with a single key | broadcast audio alarms, troubles, and | â˘Â  Accommodates wiring lengths up to 6,000 |
⢠ Can  be flush- or surface-mounted | supervisories | ft. from the control panel |
⢠ Trim ring (P/N: RA-100TR or | ||
RA-100TG) available for surface-mounting |
PHYSICAL Flush Mount:
Outside wall: 12.25âW x 11.05âH x 0.875âD (31.01W x 29.02H x 2.02D cm)
Inside wall: 9.375âW x 8.375âH x 2.0âD (23.08W x 21.03H x 5.01D cm)
Surface Mount: (Including Trim Ring)
12.25âWÂ x 11.05âHÂ x 3.0âD
STANDARDS AND CODES
The RA-2000/RA-2000GRAY complies with the following standards and codes.
- UL 864, 10th Edition: Standard for Control
Units for Fire Alarm Systems
- UL 2572, 2nd Edition: Standard for Mass
Notification Systems
- NFPA 72
(31.01W x 29.02H x 2.02D cm)
ENVIRONMENTAL Operating Temperature: 32°F to 120°F |
AGENCY LISTINGS AND
APPROVALS â˘Â  UL Listed: S3511 |
try to keep our product information
up-to-date and accurate. We cannot cover all specific applications or |
(0°C to 49°C) | ⢠ CSFM  Approved | anticipate all requirements.  All |
Humidity: 0 to 93% relative humidity | â˘Â  FDNY Approved 6162 | specifications are subject to change |
(non-condensing)
ELECTRICAL. |
without notice. | |
Operating Voltage: 24VDC | Country of origin: U.S.A. | |
Standby Current: 27mA | ||
Alarm Current: 53mA |
ORDERING INFORMATION
RA-2000: Remote Annunciator. Red
RA–2000GRAY: Remote Annunciator. Gray
OPTIONAL ACCESSORIES
RA–100TR: Red surface mount trim ring
RA–100TG: Gray surface mount trim ring