WHAT WE’RE PRODUCTS
Sub Products
Product Details
NEXGEN-RS ELITE ADDRESSABLE FIRE ALARM CONTROL PANEL
Elite RS is a versatile range of open protocol fire alarm control panels. Available with one or two detection loops capable of hosting up to 254 Hochiki or Apollo UL devices.
Elite RS uses microprocessor-based electronics to provide a flexible control system with high reliability and integrity.
Suitable for small and medium sites that require advanced fire sensing and evacuation options. Elite RS control panels can be expanded and networked to become part of much larger systems if the need arises,therefore providing a future-proof solution for any installation.
With its large graphical display and ergonomic button and indicator layout, the Elite RS control panel is simple and straightforward to understand for installers, commissioning engineers and end users alike.
Product Description
- One full SLC circuit expandable to two
- Three programmable relays
- 5.25A power supply
- Compatible with eMatrix graphics annunciator
- Powerful, network wide cause and effects
- (500 total). Fully user programmable by point or zone
- Can be networked with additional RS and/or Elite control panels
- Compatible with eView Annunciator
- Programmable through a PC connection to the panel
- Stores 1,000 last events in history log
- Model ranges include with or without a Dual-Line internal DACT
- Two programmable NAC circuits with internal synchronization support
- UL864 listed
- EN54 Approved versions also available
Standby and Alarm Current
Earth Fault Indication
A ground fault indication occurs on the Elite-RS Panel when a minimum of 30K Ohms exists between earth-ground
and either DC RTN or +24 VDC of the power-supply.
SLC Ratings
Loops Standby Alarm (mA) Description
1 160 mA @ 120 VAC 220 mA @ 120 VAC Line current for standby and alarm when
battery current is less than 30 mA.
200 mA @ 24 VDC 220 mA @ 24 VDC Battery current for standby and alarm when a
power failure condition occurs on the AC line.
2 200 mA @ 120 VAC 250 mA @ 120 VAC Line current for standby and alarm when
battery current is less than 30 mA.
270 mA @ 24 VDC 290 mA @ 24 VDC Battery current for standby and alarm when a
power failure condition occurs on the AC line.
Terminal Connection Rating
19 Loop 1 (+ IN) 32 VDC @ 250 mA
20 Loop 1 (- IN)
21 Loop 1 (+ OUT) 32 VDC @ 250 mA
22 Loop 1 (- OUT)
38 Loop 2 (+ OUT) 32 VDC @ 250 mA
39 Loop 2 (- OUT)
40 Loop 2 (+ IN) 32 VDC @ 250 mA
41 Loop 2 (- IN)