MS-9050 UD-HALF LOOP ALARM CONTROL PANEL

The Fireā€¢Lite MS-9050UD(E) is a Fire Alarm Control Panel (FACP) and Digital Alarm Communicator/Transmitter (DACT) combined into one circuit board. This compact, intelligent addressable control panel supports up to 50 addressable devices of any type of detectors and modules. With an exten- sive list of powerful features, the MS-9050UD programs just like Fireā€¢Liteā€™s larger products, yet fits into applications previously served only by conventional panels.
The MS-9050UDā€™s integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the pub- lic switched telephone network. It also allows remote and local programming of the control panel using the PK-CD Upload/ Download utility. In addition, the control panel may be pro- grammed or interrogated off-site via the public switched tele- phone network. Any personal computer with Windowsā„¢ 95 or greater, and compatible modem with a speed of 14.4 kbps or faster and Fireā€¢Lite Upload/Download software kit PK-CD, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walk-test data, current status and system voltages.
The power supply and all electronics are contained on a single Addressable circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polarity/city box transmitter. (4XTMF) New options include a UL listed printer, PRN-6F and the new IPDACT Internet Monitoring module.The FireWatch Series inter- net monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet, saving the monthly cost of two telephone lines. Although not required, the second- ary telephone line may be retained providing backup communi- cation over the public switched telephone line.
NOTE: Unless otherwise specified, the term MS-9050UD is used in this data sheet to refer to both the MS-9050UD and the MS-
9050UDE FACPs. For MS-9050UDC, refer to DF-60445.

Product Description

ā€¢ Listed to UL Standard 864, 9th edition.
ā€¢ Auto-program (learn mode) reduce installation time. Reports two devices set to the same address.
ā€¢ On-board DACT.
ā€¢ Two independently programmable Style Z (Class A) or Style Y (Class B) NAC circuits.
ā€¢ Selectable strobe synchronization for System Sensor, Whee- lock, and Gentex devices.
ā€¢ Remote Acknowledge, Silence, Reset and Drill via address- able monitor modules.
ā€¢ Two programmable relays and one fixed trouble relay.
ā€¢ Alarm verification selection per detector point.
ā€¢ Maintenance alert warns when smoke detector dust accumu- lation is excessive.
ā€¢ One-person audible or silent walk test with walk-test log and printout.
ā€¢ System alarm verification selection per detector point.
ā€¢ PAS (Positive Alarm Sequence) and Pre-signal per point
(NFPA 72 compliant).
ā€¢ Up to eight ANN-BUS annunciators
ā€¢ Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator.
ā€¢ Upload/Download (local or remote) of program and data via integral DACT.

SLC COMMUNICATION LOOP

ā€¢ Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements.
ā€¢ 50 addressable device capacity (any combination of address- able detectors and modules).
ā€¢ Compatible with Fireā€¢Liteā€™s addressable devices (refer to SLC Wiring Manual).
NOTIFICATION APPLIANCE CIRCUITS (NACS)
ā€¢ Two independently programmable output circuits. Circuits can be configured for the following outputs:
ā€“ Style Y (Class B)
ā€“ Style Z (Class A)
ā€“ Door Holder Service (cannot be used for notification appliances)
ā€“ Aux Power Source (cannot be used for notification appliances)
ā€¢ Silence Inhibit and Autosilence timer options.
ā€¢ Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.
ā€¢ Selectable strobe synchronization per NAC.
ā€¢ 2.5 A total power for NACs.

Electrical Specifications
AC Power: MS-9050UD 120 VAC, 60 Hz, 3.0 A. MS-9050UDE:
240 VAC, 50 Hz, 1.5 A. Wire size: minimum 14 AWG (2.00 mm2)
with 600 V insulation. Nonpower-limited, supervised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger
Capacity: 7-18 AH (MS-9050UD cabinet holds maximum of two
18 AH batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides con- nections for two NACs, Style Y (Class B) or Style Z (Class A). Special Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 A. End-of-Line Resis- tor: 4.7k ohm, Ā½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer to the Fireā€¢Lite Device Compatibility Document for listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, nonpower-limited, nonsupervised.

Cabinet Specifications
Door: 19.26″ (48.92 cm.) high x 16.82″ (42.73 cm.) wide x 0.72″ (1.82 cm.) deep. Backbox: 19.00″ (48.26 cm.) high x 16.65″ (42.29 cm.) wide x 5.25″ (13.34 cm.) deep. Trim Ring (TR-CE):
22.00″ (55.88 cm.) high x 19.65″ (49.91 cm.) wide.

Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00ā€ (50.80 cm.)
high x 22.5ā€ (57.15 cm.) wide x 8.5ā€ (21.59 cm.) deep.

Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 ā€“
49Ā°C/32 ā€“ 120Ā°F and at a relative humidity 93% Ā± 2% RH (non-