WHAT WE’RE PRODUCTS
Sub Products
Product Details
IFP-75 Intelligent Fire Alarm Control Panel
The IFP-75 and IFP-75HV (red) and the IFP-75B and IFP-75HVB (black) are the latest intelligent addressable FACPs (Fire Alarm Control Panels) from Honeywell’s Farenhyt™ line and are direct replacements for the IFP-50 FACP.The IFP-75 has one SLC (signaling line circuit) loop for connecting addressable detectors, which can support 75 System Sensor® IDP/SK sensors and 75 IDP/SK modules or 75 Hochiki® SD devices per loop. The total point capacity for IDP and SK devices is a maximum of 150 points per panel. Using SD devices, the total point capacity is a maximum of 75 points per panel.
The IFP-75 has the interconnection capability for up to 32 panels. The system has two modes of operation, multiple panels covering one larger building, or multiple independent buildings. The SK-NIC Network Interface Card is used to network panels together. Copper wire or fiber optic cable connectivity can be used within the same networked system.
The built-in digital alarm communicator/transmitter (DACT) is dual technology, IP and POTS. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available.
The IFP-75 has two onboard Flexput® circuits that can be configured as notification outputs or auxiliary power. There are four types of Aux power available: door holder, constant power, resettable power and sounder sync power. The IFP-75 also has form-C trouble relay, and two programmable form-C relays, along with powerful features such as drift compensation, pre- trouble maintenance alert, a built-in sensor test to comply with NFPA 72 calibration testing requirements, and a calibration trouble alert.
The IFP-75 supports a variety of devices, including RA-2000, RA-1000, or RA-100 remote annunciators, 5824 serial/parallel printer interface modules (for printing system reports), RPS-1000 power modules, and IDP, SK, SWIFT® wireless, or SD devices.
Product Description
- Complies with UL 864 10th Edition
- Built-in support for up to 75 IDP/SK detectors and 75 IDP/SK modules or 75 SD SLC devices
- Two Flexput circuits (2.5 amps max) for NAC
outputs or auxiliary power
- Selectable strobe synchronization for Amseco®, System Sensor, Wheelock®, and Gentex® devices
- 125 software zones and 125 output groups for flexible design options
- Built-in dual phone line, digital alarm communicator/ transmitter (DACT) with IP and optional cellular technologies
- Four line LCD display with 20 characters per line
- Available in 120VAC 60Hz or 240V 50/60Hz
- Built-in USB interface for quick and easy programming
- JumpStart® auto programming reduces installation time
- 13 preset notification cadence patterns
(including ANSI® 3.41)
- Allows up to 16 SBUS devices
- Two programmable relays and one fixed trouble relay
- Convenient field-upgradeable firmware
- Supports up to four SWIFT wireless gateways which can foster up to 49 wireless devices each
- Network support for up to 32 sites
- Network card allows copper network connection with a multi-mode or single- mode fiber connection
- Programmable date setting for Daylight
Savings Time
- History file with 1,000 event capacity
- Available in red or black cabinet
- Can be surface or flush-mounted
LED INDICATORS
- General Alarm (Red)
- Supervisory (Yellow)
- System Trouble (Yellow)
- System Silenced (Yellow
- System Power (Green)
KEYPAD
- 12-key numeric pad
- Acknowledge
- Alarm Silence
- System Reset
PROGRAMMING
The IFP-75 system offers several options to simplify and expedite programming. JumpStart auto programming minimizes programming required to start a new system. The built-in keypad, or the remote annunciators give on-site access to current system programming. System programming can also be accomplished using the Windows®-based Honeywell Fire Software Suite (HFSS).