IFP-1000 Addressable Fire Alarm Control Panel
The IFP-1000 and IFP-1000HV are intelligent analog/addressable fire
alarm control panels (FACPs). The basic IFP-1000 system has one
signal line circuit (SLC) loop that supports up to seven 5815XL signal
line circuit expanders. The IFP-1000HV offers the same functionality
and features as the IFP-1000 but is configured for 240 VAC operation.
IFP-1000/HV has six on-board Flexputâą circuits that can be
configured for auxiliary power, notification outputs, or for conventional
smoke detector inputs (Class A or Class B). The FACP also has a
built-in, dual-line digital fire communicator, Form C trouble relay, and
two programmable Form C relays. The firmware has powerful features
such as detector sensitivity, day/night thresholds, drift compensation,
pre-trouble maintenance alert, and calibration trouble alert.
IFP-1000/HV supports a variety of devices, including RA-1000 remote
annunciator, 5824 serial/parallel printer interface module (for printing
system reports), RPS-1000 intelligent power module, and Hochiki or
Intelligent Device Protocol (IDP) devices.
Product Description
- Built-in support for up to 127 Hochiki devices or 99 IDP detectors and 99 IDP modules, expandable to 1016 Hochiki devices or 792 IDP detectors and 792 IDP modules
- Uses standard wireâno shielded or twisted pair required
- Built-in UL listed digital communicator for remote reporting of system activity and system programming
- Central station reporting by point or by zone
- Supports Class B (Style 4) and Class A (Style 6 or Style 7) configuration for SLC, and SBUS
- Distributed, intelligent power
- Sensor sensitivity settings, day/night sensitivity setting and automatic drift compensation
- Flexputâą I/O circuits configurable for auxiliary power, notification outputs, or conventional smoke detector inputs. Notification circuits can be configured as Class A (Style Z) or Class B (Style Y). 2- and 4-wire smoke detectors can be configured as Class A (Style D) or Class B (Style B)
- Built-in annunciator with a backlit 80-character LCD display
- RS-485 bus provides communication to system accessories
- Built-in RS-232 and USB interface for programming
- Upload or download programming, event history, or detector status onsite or from a remote location using a PC and 5650/5651 Silent Knight Software Suite (SKSS)
- Improvements in SKSS delivers five times faster upload/downloads
- Built-in Form C trouble relay rated at 2.5 amps at 27.4 VDC
- Two built-in Form C programmable relays rated at 2.5 amps at 27.4 VDC
- Individual addressable devices can be tested
- SLC device locator can locate a single or multiple devices on a SLC loop
- System automatically tests addressable devices
Physical
Flush Mount Dimensions: 14.5âW x 24.75âH x 3.9âD (36.8 W x 62.9 H x 9.8 D cm)
Overall Dimensions:Â Â Â Â Â Â Â Â Â 16.2âW x 26.4âH x 4.2âD (40.6 W x 67 H x 11.8 D cm)
Weight: 28 lbs. (12.8 kg) Color: Red
Environmental
Operating Temperature: 32ÂșF â 120ÂșF (0ÂșC â 49ÂșC) Humidity: 10% â 93% non-condensing
Electrical
IFP-1000 Primary AC: 120 VRMS @ 50/60 Hz, 2.7A
IFP-1000HV Primary AC: 240 VRMS @ 50/60 Hz, 1.4A Total Accessory Load: 6A @ 27.4 VDC power-limited Standby Current: 215 mA
Alarm Current: 385 mA
Battery Charging Capacity: 7 to 35 AH
Battery Size: 18 AH max. allowed in control panel cabinet. Larger capacity batteries can be housed in RBB accessory cabinet.
Flexput Circuits
Six circuits that can be programmed individually as: Notification Circuits: 3A per circuit @ 27.4 VDC, power-limited Auxiliary Power Circuits: 3A per circuit @ 27.4 VDC, power- limited
Initiation Circuit: 100 mA per circuit @ 27.4 VDC, power- limited