WHAT WE’RE PRODUCTS

Sub Products

Product Details

IFP-1000 Addressable Fire Alarm Control Panel

The IFP-1000 and IFP-1000HV are intelligent analog/addressable fire
alarm control panels (FACPs). The basic IFP-1000 system has one
signal line circuit (SLC) loop that supports up to seven 5815XL signal
line circuit expanders. The IFP-1000HV offers the same functionality
and features as the IFP-1000 but is configured for 240 VAC operation.
IFP-1000/HV has six on-board Flexputℱ circuits that can be
configured for auxiliary power, notification outputs, or for conventional
smoke detector inputs (Class A or Class B). The FACP also has a
built-in, dual-line digital fire communicator, Form C trouble relay, and
two programmable Form C relays. The firmware has powerful features
such as detector sensitivity, day/night thresholds, drift compensation,
pre-trouble maintenance alert, and calibration trouble alert.
IFP-1000/HV supports a variety of devices, including RA-1000 remote
annunciator, 5824 serial/parallel printer interface module (for printing
system reports), RPS-1000 intelligent power module, and Hochiki or
Intelligent Device Protocol (IDP) devices.

Product Description
  • Built-in support for up to 127 Hochiki devices or 99 IDP detectors and 99 IDP modules, expandable to 1016 Hochiki devices or 792 IDP detectors and 792 IDP modules
  • Uses standard wire—no shielded or twisted pair required
  • Built-in UL listed digital communicator for remote reporting of system activity and system programming
  • Central station reporting by point or by zone
  • Supports Class B (Style 4) and Class A (Style 6 or Style 7) configuration for SLC, and SBUS
  • Distributed, intelligent power
  • Sensor sensitivity settings, day/night sensitivity setting and automatic drift compensation
  • Flexputℱ I/O circuits configurable for auxiliary power, notification outputs, or conventional smoke detector inputs. Notification circuits can be configured as Class A (Style Z) or Class B (Style Y). 2- and 4-wire smoke detectors can be configured as Class A (Style D) or Class B (Style B)
  • Built-in annunciator with a backlit 80-character LCD display
  • RS-485 bus provides communication to system accessories
  • Built-in RS-232 and USB interface for programming
  • Upload or download programming, event history, or detector status onsite or from a remote location using a PC and 5650/5651 Silent Knight Software Suite (SKSS)
  • Improvements in SKSS delivers five times faster upload/downloads
  • Built-in Form C trouble relay rated at 2.5 amps at 27.4 VDC
  • Two built-in Form C programmable relays rated at 2.5 amps at 27.4 VDC
  • Individual addressable devices can be tested
  • SLC device locator can locate a single or multiple devices on a SLC loop
  • System automatically tests addressable devices

 

Physical

Flush Mount Dimensions: 14.5”W x 24.75”H x 3.9”D (36.8 W x 62.9 H x 9.8 D cm)

Overall Dimensions:          16.2”W x 26.4”H x 4.2”D (40.6 W x 67 H x 11.8 D cm)

Weight: 28 lbs. (12.8 kg) Color: Red

Environmental

Operating Temperature: 32ÂșF – 120ÂșF (0ÂșC – 49ÂșC) Humidity: 10% – 93% non-condensing

Electrical

IFP-1000 Primary AC: 120 VRMS @ 50/60 Hz, 2.7A

IFP-1000HV Primary AC: 240 VRMS @ 50/60 Hz, 1.4A Total Accessory Load: 6A @ 27.4 VDC power-limited Standby Current: 215 mA

Alarm Current: 385 mA

Battery Charging Capacity: 7 to 35 AH

Battery Size: 18 AH max. allowed in control panel cabinet. Larger capacity batteries can be housed in RBB accessory cabinet.

Flexput Circuits

Six circuits that can be programmed individually as: Notification Circuits: 3A per circuit @ 27.4 VDC, power-limited Auxiliary Power Circuits: 3A per circuit @ 27.4 VDC, power- limited

Initiation Circuit: 100 mA per circuit @ 27.4 VDC, power- limited

Open chat
Hello 👋
Can we help you?