WHAT WE’RE PRODUCTS

Sub Products

Product Details

FAAST FLEX - 010 SINGLE PIPE ASPIRATING SMOKE DETECTOR

FAAST FLEX combines effective and reliable aspirating smoke detection with ease of design, installation, and maintenance. FAAST FLEX is ideal for enhanced and standard sensitivity applications, offering a highly flexible and cost-effective ASD solution for various SMB environments from small warehouses and elevator shafts to refrigerated storage facilities and transformer rooms.

Product Description

Single & Dual channel variants with area coverage up to 1,600m² (17,200 sq. ft) for single channel and 2,000m² (21,527 sq. ft) for dual channel
Two configuration modes:
Out-of-box with built-in user-friendly configuration and control mechanism for speedy commissioning
Extended mode for enhanced user experience using a Bluetooth interface
Modular design with in-field replaceable chamber, filter, and aspirator for ease of service and maintenance
Bluetooth interface with mobile device App for extended configuration options and rapid diagnostics
Quiet operation (45 dbA) with adjustable fan speed to suit various environments
Suitable for cold storage environments with -40 °C (-40°F) operating temperature
IP40 rating for protection against ingress of foreign bodies

Electrical Specifications
Supply Voltage : 24Vdc (18 – 30Vdc)
Maximum Power Consumption :
Single Channel Model : 400mA @24Vdc
Dual Channel Model : 450mA @24Vdc
Relays : 3 per channel, Action, Alarm and Fault 2A @30V
Detector Sensitivity Range : 0.05%obs/m to 6.56%obs/m (0.164%obs/ft – 21.5%obs/ft)
Environmental Specifications
Operating Temperature : -40 °C to 55 °C
Sampled Air Temperature : -40 °C to 55 °C
Humidity : 10-93% RH
Ingress Protection Rating : IP40
General Specifications
Flow Sensor Number : 1 per channel
Level of Alarm : Action and Alarm per channel
Fan Setting : Adjustable
Area Coverage :
Single Channel Model : 1,600m2 (17,200 sq.ft)
Dual Channel Model : 2,000m2 (21,527 sq.ft)
Pipe Network Layout :
Single Channel Model :
Linear pipe length : 1 x 105m (344 ft)
Branch pipe length :
2 x 105m (344 ft)
4 x 68m (223 ft)
Dual Channel Model :
Linear Pipe Length : 2 x 105m (344 ft)
Branch Pipe Length :
4 x 105m (344 ft)
8 x 49m (161 ft)
Sampling Holes :
Single Channel Model :
A : 5
B : 15
C : 32
Dual Channel Model :
A : 8
B : 28
C : 56
General Purpose Input (GPI) : Reset, Disable, External Fault
Out-of-Box Configuration : DIP Switches