WHAT WE’RE PRODUCTS
Sub Products
Product Details
CF-1200 2 LOOP ADDRESSABLE FIRE ALARM CONTROL PANEL
The Cooper CF1000VDS range is available as a high specification 2 loop intelligent addressable control panel, offering sophisticated functionality with simple end user operation.
The simplicity of operation, powerful cause and effect programming capability and competitive pricing make the system suitable for a wide range of small to medium sized projects.
CF1200 uses soft addressing to minimise installation time and remove the potential for error associated with manual addressing.
These panels can operate as a stand alone panel or as part of a network with the Cooper range
of CF3000 panels or other CF1200 panels (additional network card required).
The CF1200 range of panels have an integral power supply and are supplied with batteries as standard.
An extensive range of compatible intelligent addressable system ancillaries are available to work with the CF1100 range all of which incorporate an integral short circuit isolator to provide maximum protection against short circuit faults on the loop
Product Description
• Available in 2 loop version
• Up to 200 addresses per loop
• Full network capability up to 126 panels
• Soft addressing
• Large versatile touch-screen user interface
• Multi-language selection capability
• Integral battery and power supply
• Flexible cause and effect programming
• Simple to operate end user touch-screen interface
• Flexible distributed network capability
• Full range of compatible accessories
• Easy to design system cause and effect using site installer software
• Full system integrity with Cooper developed protocol
Technical Specification Code CF1200VDS
Description 2 Loop Control Panel
Standards EN54 Pt2,1997, A1:2006, EN54 Pt4,1997 A1:2002, A2:2006, EN54 Pt13: 2005
Specification
Number of Loops 1
Addresses per Loop 200
Number of Conventional
2 monitored for open and short circuit Sounder Circuits
(max 1.5A combined)Auxiliary Fire Routing Equipment
Output (Monitored) 24V dc 30mA (max)
Auxiliary Fire Protection Equipment
Output (Monitored) 24V dc 30mA (max)
Auxiliary Fault Routing Equipment Output (Monitored)
12V dc 30mA (max) System Operating Voltage 24V dc (nom)
Mains Input Supply 230V ac +10% / -15%
Class Change Facility Terminals for connection of external contacts, can also be instigated via input interface
Auxiliary Relay 1 set of changeover contacts operate inevent of fire condition
Output Ports RS485, RS232 for connection of repeatersetc
Standby Duration Dependant on loop loading and battery configuration
Battery 2 x 7Ah
Environmental Operating Temperature -5°C to +40°C
Humidity (Non Condensing) 0 to 75% RH
Physical Construction Back Box – Steel
Dimensions (H x W x D) 375mm x 357mm x 95mm
Weight 8kg
Ingress Protection IP30
Cable entries Top: cable knockouts (20mm) Back: cable aperture
System Networking Fully Net-workable up to 126 panels (requires additional network card, per panel)