WHAT WE’RE PRODUCTS

Sub Products

Product Details

AX-CTL-1 -1 LOOP FIRE ALARM CONTROL PANEL

Available in two (2) configurations, AX-CTL-1 (small/ compact enclosure) or AX-CTL-1L (standard AxisAX Series sized enclosure), the AX-CTL-1 (1L) Intelligent Single Loop Fire Alarm Control Panel is a member of the industry leading AxisAX Series Intelligent Fre Alarm Control Panels by Advanced. The AX-CTL-1 (1L) contains the identical features as the Advanced AX- CTL-2 (2 loop) and AX-CTL-4 (4 loop) Intelligent Fire Alarm Control Panels, and is ideally suited to smaller applications. However, as a member of the Axis AX Series product line the AX-CTL-1 (1L) can easily be utilized in larger applications due to its integral peer-to- peer networking capabilities.

Product Description

• Automatic Drift Compensation per Detector
• Automatic Detector Testing w/Maintenance Alert
• Alarm Verification and PAS
• Style 4, 6 & 7 SLC Operation (supports loop powered technology)
• Class A or B NAC Circuits
• Voltage Regulated NACs (compatible with most Listed NAC devices)
• Synchronization of Audibles and Visuals (Panel or Network Wide)
• “Auto-Learn/Loop Detection” Programming
• Built-in Intelligent Multi-Meter
• Optional ipGateway for text and email status notification
• Optional Integral or Portable Printer
• SLC Circuit Compatibility with Xtralis VLC-400

Operating Voltage 120 VAC (1.4A) – 240 VAC (0.7A), 50/60Hz System-Brown-Out 98 VAC nominal
Battery Circuit Charging Voltage Temp. Compensated Charging Current Battery Derating Factor Battery Capacity Battery Fuse 27.4 VDC nominal 2 Amp 0.83A 7 Ah (minimum), 48 Ah (maximum) 5A @ 240 VAC, Time Delayed, Ceramic, High Breaking (In-line Wire Link)
Fire, Supervisory, and Trouble Relays Type Rating
Trouble Relay (Power Limited – when utilizing system power)
Form “C” 1A @ 30 VDC/VAC
Normally Active (fail-safe operation) Auxiliary Power Outputs Resettable Voltage Current
Reset Time Non-Resettable
Voltage Current (Power Limited) 24 VDC .5A
10 – 15 Seconds 24 VDC .5A
Humidity 85% RH Temperatures
Operating Recommended Room
320F – 1200F (00C – 490C)
600F – 860F (150C – 270C)
Enclosure Dimensions
AX-CTL-1
AX-CTL-1L
19.1”H x 16”W x 5.3”D
24.1”H x 16”W x 6.3”D
SLC Loop
Class (Style)
Voltage
Minimum Return Voltage
Current
(Power Limited)
Class A or B (Style 4, 6 or 7)
24 VDC
17 VDC
.5A
NAC Circuits
Class (Style)
Voltage
Minimum Return Voltage
Current
Maximum Voltage Drop
Maximum Line Impedance
(Power Limited)
Class A or B
24 VDC (filtered and regulated)
16 VDC
2A (each)
3 VDC
1.5Ί
RS232
Baud Rate
Parity
Data Bits
Stop Bits
Supervised, Optically Isolated
9600
None
81
Base Card Operating Current
AX-CTL-1 (1L)
Quiescent Alarm
110 mA 195 mA