WHAT WE’RE PRODUCTS
Sub Products
Product Details
6 ZONE 240W AMPLIFIER-A-EVAC-6Z-240W
6 Zone EVAC Controller
Built-in 240W class-D amplifier
Built-in EVAC and alert voice message by SD card
Integration of EVAC controller, paging system, PA system & BGM system together
Zone capacity of 120 zones by cascaded 19 routers
Product Description
- 6 Zone EVAC Controller
- Built-in 240W class-D amplifier
- Built-in EVAC and alert voice message by SD card
- Integration of EVAC controller, paging system, PA system & BGM system together
- Zone capacity of 120 zones by cascaded 19 routers
Model Number | A-EVAC-6Z-240W |
---|---|
Rated Power Output | 240W |
Fireman Microphone | 5Mv, 600Ω |
Line 1-2 Inputs | 385mV, 10kΩbalanced Combo |
Line 3-6 Inputs | 350mV, 10kΩ, RCA |
Frequency Response | 80Hz~20kHz |
THD | <1% at RMS,1KHz |
S/N Ratio | >70dB |
Speaker Output | 100V AB 8 zone speaker outputs |
REC Output | 200mV |
Control Input & Output | 8 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact 8 programmable control outputs: 0V closed contact; Control output for fault & EVAC: 0V closed contact; Reset control input: 0V closed contact |
Voice Message | MP3 or WMA format, two separate players of SD card with protection cover, programmable voice message up to 255, 10 years valid |
Event Record | HEX format, Hard Flash memory, events up to 1000 records, 10 years valid |
Operation Environment | Operation Temp: +5℃ ~ +40℃; Store Temp: -20℃ ~ +70℃; Operation Humidity: <95% |
Power Consumption | 600W |
Power Supply | AC230V or 115V & DC24V battery inputs, 50-60HZ |
AC Fuse | 250V/6.3A, slow type and restorable fuse |
Dimension | 484(W)×132(H)×449(D) mm |
Weight | 24kg |