RE-2558 8 ZONE UL LISTED FIRE ALARM CONTROL PANEL

The microprocessor based UL listed 8 Zone conventional fire alarm control panel, the system has 16 X 2 LCDcharacter, 8 zones detection circuit,3 common potential free contacts &2 common NAC sounder output, inbuilt Rs-485 for repeater connectivity, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.
RE-2558 fire alarm control panel is designed with unique protocol to be used for small & medium establishments, Schools, hospitals, hotels, banks, residential / commercial building, and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.

Product Description

Switched Mode Power Supply.
Modular Construction
Auto Resettable Fuse
Surge Protection for all Input and outputs.
Programmable AC loss delay/Trouble Remainder/Alarm Verification
Battery polarity reversible protection
Surface Mount Technology
Over All current consumption is low.
Fully complies with UL -864 and NFPA-72.
Rugged CRCA sheet with powder coated finish.
Operates on 110 – 220v 50 /60 Hz, AC Mains power supply.
16×2 Dot Matrix LCD Display.
4/8 Class B Style ‘B ‘ or Style ’C’ initiating device circuit (IDC).
All zones accept smoke detectors and any normally open contact device.
Any Zone can be configured as Alarm or supervisory Zone.
2ClassBNotificationApplianceCircuits(NAC).
NAC shall be programmed as silenceable or Non Silenceable.
Supervisory Zone shall be Latching or Resettable.
Standby (battery) backup 24v DC power supply with built in charger
Error free Fire / Fault status in unambiguous colored LED indication.
System ON indication.
Main, Standby status audible and visual indication.
Battery Low visual warning with audible tone.
FormC relays for fire, fault and supervisory.
Resettable / Steady 24V D.C. Output.
RS 485 Communication facility (Optional).
Lamp Test facility.
All field wiring circuits are Power limited except 110 – 220v AC and Battery.
All field wiring circuits are supervised.
Walk Test facility.
Zone Isolation facility with loop voltage cut off.
Earth fault annunciation facility at 0 ohms.
AC Low voltage cutoff.
Programmable AC loss delay / Alarm verification / Trouble reminder.

Electrical Specification
Primary Power
120 – 220VAC ± 10%, 50 Hz, 2.5Amps.
Standby Power
24V D.C (2 Nos of 12v, 12Ah Sealed Lead acid battery).
Quiescent current: 120mA

Initiating Device Circuits
All zones are Class B Style B/C operation (Programmable).
Normal Operating Voltage: 14 – 21 VDC.
Alarm Current: 15 – 30mA.
Short Circuit Current: 45mA Maximum.
Loop resistance: 100 ohms Maximum.
End-Of-Line Resistor: 3K9, 1/2watt
Standby Current: 7mA (2mA for Detectors)
Operating Condition
Operating Temperature 0 – 49° C/32-120° F.
Relative Humidity 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F.
Charging Circuit
Charging Voltage 28.2V, ±0.5V
Charging Current 800mA (Max.). Notification Appliance Circuits
Class B Style – Y wiring
Operating Nominal Voltage: 24VDC
Special Application Current for all NACs: 1.2Amps (0.6A per circuit)
Line Drop: 1.8V
End-Of-Line Resistor: 3K9, 1/2watt
D.C. Output
Supervised 24VDC regulated, 300mA Max.
Common Relays
Type : Form C
No of Relays : 3
Relay Contact Rating : 2Amps @ 30 VDC,
0.5Amps @ 125VAC.
Power Factor : 1.0
Mechanical Specification
Dimensions :(440W X 340H X 120D)
Color : Red / White
Construction :18 Gauge (1.22mm) CRCA sheet with powder-coated Finish
IP Rating :IP50
Cable Entry :11xø19mm Knockout in top of the cabinet
10xø22.25mm Knockout in top of the cabinet