MS-9600 LS- 1 LOOP ALARM CONTROL PANEL

Fire•Lite’s MS-9600LS(E) and MS-9600UDLS(E) are compact, cost effective, intelligent addressable FACPs (Fire Alarm Control Panels) with an extensive list of powerful features. The combination of Fire•Lite’s newer series devices and legacy 300 Series devices, along with the MS-9600LS(E) or MS-9600UDLS(E) FACP, offer the latest in fire protection technology. LiteSpeed™ is a patented technology that polls 10 devices at a time looking for new or different information. When new information is found at a specific address, the system polls that device several times for any new data. This improvement allows a fully loaded panel with up to 636 devices to report an incident and activate the notification circuits in under 10 seconds. With this polling scheme, devices can be wired on stan- dard twisted, unshielded wire up to a distance of 10,000 feet per loop. Each Signaling Line Circuit (SLC) loop supports up to 159 addressable detectors including photoelectric, photoelectric with heat, beam, ionization, photoelectric duct, fixed heat, fixed heat with rate-of-rise, and fixed high-heat detectors. It also supports up to 159 addressable modules including monitor (two-wire detector, normally open devices), dual-monitor functions (two monitor circuits from one module, two addresses used), multi-monitor (multiple monitor cir- cuits from one module, multiple addresses used), control (for Notifi- cation Appliance Circuits), and relay (two Form-C) modules.
The FLPS-7 power supply is a separate board while all other elec- tronics are contained on a single main circuit board. Both boards are mounted to a quick-removable chassis and housed in a metal cabi- net. The backbox can be installed allowing field wiring to be pulled. When construction is completed, the chassis with the electronics can be quickly installed with two bolts.
The MS-9600UDLS(E) includes a factory-installed 2 Digital Alarm Communicator Transmitter. The DACT transmits system status (alarm, troubles, AC loss, etc.) to a Central Station via internet (optional IPDACT installed) or the public switched telephone net- work.
Optional modules, which plug into the main circuit board, are avail- able for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, digital alarm communicator/transmitter, SLC expansion module, local and remote upload/download software and remote power expansion.
FM APPROVED to UL ANSI 864

Product Description

Special Features
• Easy mount chassis.
• 7 amp switching power supply.
• Large enclosure allows 18 amp-hour batteries
• 2 plug-in communicator standard with MS-9600UDLS/E.
• Optional IPDACT Internet Protocol Digital Alarm Communicator/ Transmitter
• Four Style Y (Class B) or two Style Z (Class A) NAC circuits.
• Selectable strobe synchronization per NAC for
System Sensor, Wheelock, and Gentex devices.
• Certified for seismic applications when used with the appropriate seismic mounting kit
• Seamless integration between fire and mass notification with the ECC-50/100 Emergency Command Center via ANN-BUS con-
nections.
• ECC-FFT Firefighter Telephone Option
• ANN-BUS for connection to following optional modules
Note: cannot be used if ACS annunciators are used.
• Local piezo sounder.
• Waterflow (non-silenceable) selection per monitor point.
• System alarm verification selection per detector point.
• PAS (Positive Alarm Sequence) and presignal delay per point
(NFPA 72 compliant).
• Optional 4XTMF module (conventional reverse polarity/city box transmitter).

– ANN-80(-W) Remote LCD Annunciator
– ANN-I/O LED Driver Module
– ANN-S/PG Serial/Parallel Printer Module

• Primary input power:
120 VAC, 50/60 Hz, 3.0 A.
240 VAC, 50 Hz, 1.5 A.
•Battery: 27.6 VDC @ 1.0 A (max).
Maximum battery charger capacity: 26 AH. Minimum battery: 12 AH.
MS-9600LS cabinet holds maximum of two 18 AH batteries.
• Communication Loop: 24 VDC nominal, supervised and power- limited.
• Notification Appliance Circuits: terminal block provides connec- tions for four Style Y (Class B) or two Style Z (Class A) NACs. Maximum signaling current per circuit: 3.0 amps special applica- tion, 300mA regulated.
End-of-Line Resistor: 4.7 K ohms, ½ watt (P/N 71252 UL listed)
for Style Y (Class B) NAC. Supervised and power-limited.
Refer to panel documentation and Fire-Lite Device Compatibility
Document for listed compatible devices.
• Two Programmable Form-C Relays and One Fixed Trouble
Form-C Relay: Contact rating: 2.0 A @ 30 VDC (resistive)
0.5 A @ 30 VAC (resistive).
• Four-wire Resettable Special Application Power (24 VDC nomi- nal): Up to 1.5 A for powering four-wire smoke detectors. Power- Limited, non-supervised.
Refer to Fire-Lite Device Compatibility Document for listed com- patible devices.
• Non-resettable Special Application Power #1 (24VDC nominal) TB3, Terminals 3 (+) & 4 (-):
Maximum ripple voltage: 10 mVRMS
Total DC current available from each output is up to 1.5 A.
Power-limited, non-supervised.
• Non-resettable Special Application Power #2 (24VDC nominal) TB3, Terminals 5 (+) & 6 (-):
Maximum ripple voltage: 10 mVRMS
Total DC current available from each output is up to 1.5 A.
Power-limited, non-supervised.
NOTE: Although each Special Application power output can deliver 1.5
A individually, the total power output from these circuits cannot exceed
1.5 A in standby. The total Alarm output for all Special Application power and NAC circuits cannot exceed 7 A.

Cabinet Specifications
Door: 19.26″ (48.92 cm.) high x 16.82″ (42.73 cm.) wide x 0.67″ (1.70 cm.) deep. Backbox: 19.00″ (48.26 cm.) high x 16.65″ (42.29 cm.) wide x 5.21″ (13.23 cm.) deep. Trim Ring (TR-CE): 22.00″ (55.88 cm.) high x 19.65″ (49.91 cm.) wide.